Coordinated Optimization of Recloser Placement and PV Allocation for Protection Sensitivity and Reliability

Traditional grid planning usually treats protection device placement and photovoltaic allocation as separate problems. The rapid expansion of distributed generation introduces bidirectional power flows that disrupt traditional unidirectional protection coordination. The study evaluates the impact of photovoltaic integration…

Traditional grid planning usually treats protection device placement and photovoltaic allocation as separate problems.

The rapid expansion of distributed generation introduces bidirectional power flows that disrupt traditional unidirectional protection coordination. The study evaluates the impact of photovoltaic integration on protection performance and network reliability.

During test evaluations under Scenario 2, Bus 29 emerges as the best site for a photovoltaic installation sized at 70% of the aggregate network load, which leads to enhanced voltage characteristics. In Scenario 3, with the recloser optimally placed on Line 1, the energy not supplied, system average interruption frequency index, and system average interruption duration index values are 36.82 MWh per year, 5.58 interruptions per customer per year, and 9.12 hours per customer per year, respectively.

Short-circuit analysis of faults downstream of cut-out fuses confirms that the recloser-fuse coordination constraint is satisfied both with and without photovoltaic integration. The method incorporates analytical short-circuit current calculations to determine the critical distributed generation capacity required to maintain protection sensitivity and avoid protection maloperation.

Results demonstrate the existence of a permissible distributed generation capacity threshold beyond order to ensure proper protection coordination and preserve the fuse-saving strategy, the penalty function approach embeds the recloser and cut-out fuse coordination constraint directly into the objective framework.

Network Reliability and Performance Metrics
Scenario / Parameter Optimal Location Capacity / Value
Scenario 2 (PV Unit) Bus 29 70% of total network load
Scenario 3 (Energy Not Supplied) Line 1 (Recloser) 36.82 MWh/yr
Scenario 3 (SAIFI) Line 1 (Recloser) 5.58 int/cus/yr
Scenario 3 (SAIDI) Line 1 (Recloser) 9.12 h/cus/yr

Findings validate that efforts to enhance reliability require careful alignment with protection limits to facilitate a secure and dependable shift toward decentralized power networks. A search algorithm handles the optimization task, and tests on the IEEE 33-bus test system validate the suggested technique.

Distributed generation introduces bidirectional power flows that fundamentally disrupt traditional unidirectional protection coordination, creating a risk of relay maloperation if capacity thresholds are exceeded.

The framework evaluates and aims to improve reliability indices including SAIFI, SAIDI, and annual energy not supplied, while maintaining proper coordination between reclosers and cut-out fuses.